通风气楼通风计算方法

时间:2021/2/21 9:38:42

Calculation Method Of Ventiation Ventilation Clearstory?

1、计算方式∶G=3600up*Ap*2g*hp*yp*(yj-yp) G-通风气楼通风量(Kg/h) Up-通风气楼流量系数,一般取0.56 Ap-通风气楼喉口面积(m2),取3.2m2 g-重力加速度(m/S2),取9.81 hp-通风气楼高度中心至中和界的高差(m) yp-排风温度下的空气容重(Kg/m3) yj进风温度下的空气容重(Kg/m3)中和界位置的确定hj/hp= (Ap/Aj) *2 hj-进风窗或们中心高度至中和界的高差(m) Ap-通风气楼喉口面积(m2) Ap-进风窗或门面积(m2)?Aj换气量建筑物体积(m)×换气次数(次/时)

?2、换气量=建筑物体积(m3)×换气次数(次/时)?1、The calculationmethod:G=3600up*Ap*2g*hp*yg*(yj-yp) G-ventilated building ventilation volume(kg/h)?Up-ventilated building folow coefficient,generallytake 0.56 Ap-Ventilation clearstory theoat area(square meters),3.2 meters g-acceleration of gravity(m/S2),9.81?hp-elevationventilated building height to the neutralization Community Center(m) yp-air dengsity air temperature(Kg/m3) yj-into the air density air temperature(kg/m3) Determination of neutral position:hj/hp=(Ap/Aj)*2?hj-head into the wind window or door to neutralize the circle centerheight(m) Ap-Ventilation clearstory throat area(square meters) Aj-air inlet window or door area(square meters)?2、The ventilationvolume(M=building3)×ventilation frequency(times/